| Dissolved Gas Analysis | Interpretation | Acceptable Limits |
| Hydrogen* H 2 |
Thermal decomposition of the cellulose insulation material - overheating condition. | 500 ppm (0.05%) (Max.) |
| Methane* CH 4 |
Overheating or other fault conditions have occurred or exist inside the transformer. | 100 ppm (0.010%) (Max.) |
| Ethane* C 2H 6 |
Low energy arcing has occurred or exists inside the transformer. | 50 ppm (0.005%) (Max.) |
| Ethylene* C 2H 4 |
Transformer is operating hot or localized overheating has occurred or exists. | 50 ppm (0.005%) (Max.) |
| Acetylene* C 2H 2 |
High energy arcing has occurred or exists inside the transformer. | 0 ppm (0.00%) (Max.) |
| Oxygen O 2 |
Thermal decomposition of the cellulose insulation material - overheating condition. | 20,000 ppm (2.00%) (Max.) |
| CarbonMonoxide* CO |
Thermal decomposition of the cellulose insulation material - overheating condition. | 1,000 ppm (0.10%) (Max.) |
| Carbon Dioxide CO 2 |
Thermal decomposition of the cellulose insulation material - overheating condition. | 10,000 ppm (1.00%) (Max.) |
| * Combustible Gas |
||
| Oil Screen Analysis |
Interpretation | Acceptable Limits |
| Moisture Content | Reveals if transformer tank is sealed or cellulosic breakdown via the level of water present. | 25 ppm ↓ 69KV XFRM (Max.) 35 ppm ↑ 69KV XFRM (Max.) |
| Interfacial Tension | Reveals the presence of sludge. Precursor to the insulation’s failure to properly cool the unit. | 24 dyne/cm (Min.) |
| Acid Number | The amount of acidic or alkaline material present. | 0.20 mg KOH/g-oil (Max.) |
| Color Number | Elevated number indicates oil contamination or deterioration of the oil. | 0.5 (New Oil) – 8.0 (Worse case ) |
| Dielectric Breakdown | Reveals conductive contaminants in the oil such as metallic cuttings, fibers or free water. | 24 KVAC (Min.) |
| Specific Gravity | Helps reveal if oil has been mixed with other fluids. | Approx 0.875 @15°C |
| Power Factor | Reveals leakage current through oil. Elevated power factor reveals moisture, resins or fuel oils. | 0.5% ↓ 69KV XFRM @ 25°C 1.0% ↑ 69KV XFRM @ 25°C (Max.) |